• GIS MV cubicles SF6 LBS
  • GIS MV cubicles SF6 LBS
  • GIS MV cubicles SF6 LBS
  • GIS MV cubicles SF6 LBS
  • GIS MV cubicles SF6 LBS
  • GIS MV cubicles SF6 LBS

GIS MV cubicles SF6 LBS

Breaking Capacity: High Voltage Circuit Breakers
Operation: Energy-storage Type
Speed: Normal Type Circuit Breaker
Arc-extinguishing Medium: Vacuum
Installation: Fixed
Structure: Vcb
Customization:
Gold Member Since 2020

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company

Basic Info.

Poles Number
1-3
Type
Circuit Breaker
Function
Circuit-Breaker Failure Protection
Certification
ISO9001-2000

Product Description

 GIS MV cubicles SF6 LBS

 
Specification:            

Load break switch+fuse combination set
Load break switch top unit
Load break switch lower unit
GSC-12/24/36kV serie is 3 position SF6 load break switch designed for indoor and outdoor medium voltage switchgear-air insulated panel,adopted SF6 gas as arc-extinguishing and insulation medium, The epoxy resin enclosure ensures good insulation and resistance to moisture and environmental pollution.

characteristics :
Strictly follow the standards of IEC60256-1, IEC60420,GB3804-1990,1997, GB16926,etc....
Small volume ,easy installation and operation
Great adaptability to surrounding environment,suitable for high altitude.

Mechanical Data

Item NO. Name Unit Technical parameters
Load break switch panel
1 Rated Voltage Un kV 12 24 36
2 Rated Frequency Hz 50 50 50
3 Rated Current A 630 630 630
4 Rated Load Breaking Current A 630 630 630
5 Rated Short Time Withstand Current(rms) kA 20 20 20
6 Rated Short Time Duration s 3 3 3
7 Rated Peak Withstand Current  kA 50 50 50
8 Rated Closed Switch - Off Current A 630 630 630
9 Rated Cable Charging Breaking Current A 10 10 10
10 Rated Active Load Breaking Current A 630 630 630
13 Earthing Switch 2s Short Time Withstand Current  kA 20 20 20
14 Rated Short-Circuit Current Making Times  times 2 2 2
15 Rated Current Breaking Times times 10 10 10
16 Mechanical Endurance  Load Break Switch times 3000 3000 3000
Earthing Switch times 2000 2000 2000
17 SF6 gas anual leakage rate≤   /year 0.10% 0.10% 0.10%
18 Rated Insulation Level Unit Technical parameters
1min Power Frequency withstand voltage(rms) On isolating distance kV 48 60 110
Phase to Phase  kV 42 50 85
Phase to Earth kV 42 50 85
Lightning impulse withstand voltage(peak) On isolating distance kV 85 145 215
Phase to Phase  kV 75 125 185
Phase to Earth kV 75 125 185


GIS MV cubicles SF6 LBS
GIS MV cubicles SF6 LBS
GIS MV cubicles SF6 LBS
GIS MV cubicles SF6 LBS
GIS MV cubicles SF6 LBS
GIS MV cubicles SF6 LBS
GIS MV cubicles SF6 LBS
GIS MV cubicles SF6 LBSGIS MV cubicles SF6 LBS

Company website:

http://feiteelectric.en.made-in-china.com

 

Comtact person:Willow Chen


Professional, Creative, Good quality and Excellent service

 

Welcome your inquiry, Welcome our cooperation!

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now