Main Technical Data | ||||
Rated voltage | kv | 24 | ||
Rated current | A | 1250/1600 | ||
Rated frequency | Hz | 50 | ||
Rated short-circuit breaking current | KA | 25/31.5 | ||
operations of shortcircuit making current interruption | times | 30 | ||
Rated short-circuit making current | KA | 60/80 | ||
Rated short-time withstnd and current(4S) | KA | 25/31.5 | ||
Rated single capacitor bank breaking current | A | 630 | ||
rated back-to-back capacitor bank breaking current | A | 400 | ||
short-time(lmin) power-frequency withstand voltage | KA | 79 | ||
rated lightring impulse withstand voltage (peak) | kA | 145 | ||
ciruit resistance at rate contact force | μΩ | ≤20 | ||
Mechanical life | times | 10000 | ||
contact closing force due to bellows and atmosphere | N | 120±50 | ||
counterforce at rated contact force | N | 200±50 | ||
Contact erosion limit | mm | 3 | ||
shelf life | years | 20 | ||
part discharge | pc | ≤5 | ||
rated operating sequence | 0-0.3-CO-180s -CO | |||
MECHANICAL DATE OF CIRCUIT-BREAKING EQUIPPED WITN THE INTERRUPTERS | ||||
rated cintact stroke | mm | 13±1 | ||
contact connection stroke | mm | 4±1 | ||
average opening speed | m/s | 1.3±0.2 | ||
average closing speed | m/s | 0.6±0.3 | ||
added contact force | N | 2500/3150±200 | ||
bounce duration of cintact closing | ms | ≤2 | ||
out of simultaneity of contact closing and opening | ms | ≤1 | ||
max. overtravel | mm | ≤2 |