Customization: | Available |
---|---|
Breaking Capacity: | 12kv |
Operation: | Electric Type |
Still deciding? Get samples of US$ 54.99/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
PRODUCT DESCRIPTION:
ZW8 ZKTD630/12-16
ZW8 ZKTD630/12-12.5
ZW8 ZKTD630/12-20
Main Technical Data | ||||
Rated voltage | kv | 12 | ||
Rated current | A | 630 | ||
Rated frequency | Hz | 50 | ||
Rated short-time power frequency withstand voltage(1 min) | kv | 42 | ||
Rated lightning impulse withstand voltage | kv | 75 | ||
Rated short-circuit breaking current | KA | 12.5/20/16 | ||
Rated short-circuit making current (peak) | KA | 31.5/50/40 | ||
Rated operations of short-circuit breaking current interruption | times | 30 | ||
Rated single capacitor bank breaking current | A | 400 | ||
Rated short-time withstand and current | KA | 12.5/20/16 | ||
Rated peak withstand current | KA | 31.5/50/40 | ||
Rated duration of short-circuit | s | 4 | ||
Mechanical life | times | 10000 | ||
contact closing force due to bellows and atmosphere | N | 70±40 | ||
counterforce at rated contact force | N | 120±50 | ||
circuit resistance at rate contact force | μΩ | ≤20 | ||
shelf life | years | 20 | ||
Contact erosion limit | mm | 3 | ||
Weight of moving parts | kg | ≤0.7 | ||
MECHANICAL DATE FOR MATCHED VACUUM SWITCHGEAR | ||||
rated contact stroke | mm | 9±1 | ||
average opening speed | m/s | 1.0±0.25 | ||
average closing speed | m/s | 0.65±0.15 | ||
added contact force | N | 1600±100 | ||
contact bouncing duration at closing operation | ms | ≤2 | ||
contact bouncing bank amplitude of opening operation | mm | ≤2 | ||
three-pole simultaneity | ms | ≤1 |
If you need or want to learn more about products, please feel free to contact me .