40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker

Product Details
Customization: Available
Electricity Type: Vacuum
Number of Pole: Fixed
Manufacturer/Factory & Trading Company
Gold Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Number of Employees
116
Year of Establishment
2006-09-05
  • 40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
  • 40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
  • 40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
  • 40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
  • 40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
  • 40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
Find Similar Products
  • Overview
  • Product Description
  • Company Profile
  • Certifications
  • Packing
  • FAQ
Overview

Basic Info.

Model NO.
VEP546A(VEP1600/2000/40.5-31.5)
Phase
3
Main Circuit Rating Voltage
40.5
Main Circuit Rating Current
1600/2000
Type
DC/AC Vacuum Contactor
Name
Embedded poles
Shelf life
20years
Afterserivce
Yes
Certification
ISO9001-2000
Transport Package
Pallet, Carton
Specification
Circuit-Breaker Failure Protection
Trademark
Feite
Origin
China
HS Code
8535900090
Production Capacity
600000/Year

Product Description

Product Description

VEP546A(VEP1600/2000/40.5-31.5)


Main Technical Date

Main Technical Data
Rated voltage                                                              kv 40.5
Rated current                                                              A 1600/2000
Rated frequency                                                          Hz 50
Rated short-circuit breaking current                                KA 31.5
operations of short-circuit making current interruption times 30
Rated short-circuit making current       KA 80
Rated short-time withstand and current(4S) KA 31.5
Rated single capacitor bank breaking current          A 630
rated back-to-back capacitor bank breaking current A 400
short-time(1min) power-frequency withstand voltage KA 95
rated lightning impulse withstand voltage (peak) kA 185
circuit resistance at rate contact force μΩ 20
Mechanical life                                            times 10000
contact closing force due to bellows and atmosphere N 250±50
counterforce at rated contact force N 350±50
Contact erosion limit mm 3
shelf life years 20
part discharge                                  pc 5
rated operating sequence   0-0.3-CO-180s -CO
MECHANICAL DATE OF CIRCUIT-BREAKING EQUIPPED WITN THE INTERRUPTERS
rated contact stroke  mm 18±1
contact connection stroke mm 4±1
average opening speed m/s 1.6±0.2
average closing speed m/s 0.8±0.3
added contact force N 3150±200
bounce duration of contact closing ms 2
out of simultaneity of contact closing and opening ms 1
max. overtravel mm 2
 



40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
 

Company Profile

ABOUT OUR COMPANY

Wuhan Feite Electric Co.,Ltd is located at Wuhan city, Hubei Province which is the Eastcenter part of China. lt is specialized in producing vacuum interrupter and vacuumembedded poles.The company has developed 1.14KV-40.5KV vacuum switch tubes morethan 300 types,which can be widely used for various vacuum circuit breaker, vacuumcontactors, vacuum load breaker switches, auto re-closers,RMU etc.The company has full sets vacuum producing and testing equipment,with annualproduction of 600,000 vacuum tube production capacity, As an ISO09001:2008 certifiedcompany,our production process strictly conforms to quality management system.Wuhan Feite Electric Co.,Ltd is always supply you good quality products with reasonableand competitive prices.



40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker


40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker


3> Different Types Vacuum Interrupter and Embedded Poles
40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker

 
Certifications

 


40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker

Vacuum Interrupter and Embedded Poles Stock
40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker


6> Company Introduction
40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker
 
Packing
40.5 High Voltage Embedded Pole for Vacuum Circuit Breaker

 

FAQ

1. Precheck before putting it into use.
Check id packing is in good condition. Check the appearance of vacuum interrupter and
Whether it corresponds to the test certificate after uppacking. When shaking the interrupter, the ceramic envelop should be integrated.Power frequency withstand voltage should be tested before operating vacuum interrupter. Clean the surface with a dry colth or alcohol damped cloth before testing. The normal way for testing is an follows: when in the clearance between open contacts applies with 70 percent of rated power frequency withstand voltage within 1 min. The vacuum interrupter will be qualified if there is no sudden change and trip phenomena in the pointer of the vacuum interrupter.

 
2. Mounting of vacuum interrupter
a.Clean the surface of vacuum interrupter with cotton or alcohol dipped silk cloth before mounting. Meanwhile clean the conducting pole and surface of electric connection in order that the vacuum interrupter can have good electric contact with the equipment.b.The interrupter should be adjusted in the line with the equipment after mounting. The mechanical date related to the interrupter must meet the given specification.

3.In mounting, attention should be paid to the following:
a.When operating, guide unite unit must be provided for the interrupter. The coaxality of moving conducting pole and axial line of interrupter must meet the requirement. There should not be torque force applied on the bellow.
b. When mounting, it is forbidden to beat or strike the interrupter envelop with hard things in case crack may occur to cause air leakage.
c.Take care to assure that the conducting pole must be coaxial with interrupter, and that the conducting pole must be vertical on the face of fixed end
d.Take care not to disassemble the interrupter repeatedly to prevent screw from slipping. There should not be twisting on the moving conducting pole and over press on bellow to avoid that any torque force and scratch may occur to bellow to reduce its service life.
e.During mounting, the force applied on the face of both ends should not go beyond the static relief pressure stipulated in the specification.

 

4. Application.
a. Check the vacuum interrupter periodically by the way power frequency withstand voltage. For this, please see subclause
b. Periodically check how burnout is going on for contacts. When it comes to the burnout mark of moving conducting pole, it shows that the vacuum interrupter has finished its electrical endurance, and it should be replaced.