Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. |
Item |
Unit |
Value |
||
1 | Rated voltage | KV | 40.5 | ||
2 | Rated insulation level |
Rated lighting impulse withstand Voltage (peak) |
KV | 185 | |
1min Short-time power frequency withstand voltage(1min) |
KV | 95 | |||
3 | Rated short circuit breaking current |
KA | 25 | 31.5 | |
4 | Rated current | A | 1250/1600 | 1250/1600/2000 | |
5 | Rated withstand current(peak) |
KA | 63 | 80 | |
6 | Rated operations of short circuit breaking current interruption |
20 | |||
7 | Rated duration of short circuit | S | 4 | ||
8 | Rated operating sequence |
-0.3S--180S- Opening-0.3S-closing opening-180S-closing opening |
|||
9 | Closing and brake device circuit of power supply voltage |
V | AC,DC220 AC,DC110 | ||
10 | Closing time | ms | 50~100 | ||
11 | Opening time | ms | 30~60 | ||
12 | Rated breaking current( a capacitor) |
A | 630 | ||
13 | Rated breaking current(back to back capacitor) |
A | 400 | ||
14 | Mechanical life | 20000 |
No. |
Item |
Unit |
Value |
1 | Contact distance | mm | 18±1 |
2 | Contact over travel | mm | 6±1 |
3 | Average opening speed | m/s | 1.6±0.2 |
4 | Average closing speed | m/s | 0.8±0.2 |
5 | Contact bouncing duration at closing operation |
ms | ≤2 |
6 | Operating mechanism type | 3AVSpecial spring mechanism | |
7 | Three-pole simultaneity | ms | ≤2 |
8 | Conductive circuit resistance of each phases |
μΩ | <45 |