ZN63A(VS1)-12 indoor high voltage vacuum circuit breaker



Overview
VHE-12 vacuum circuit breaker with 12KV rated voltage,indoor distribution device of three-phase ac 50HZ. Available for industrial and mining enterprises,power plant and substation in electric equipment protection and control,Especially suitable for the fields of free oil, less maintenance and frequent operation. It can be configured in the centrally installed switchgear,double switchgear,fixed switchdaer for control and protection of the high voltage electrical equipment. It meets the standard of GB1984, DL403, IEC56, 694 publication. The main characteristics of the product are:
1.Circuit breaker operating mechanism and circuit breaker ontology integration design,The overall layout is reasonable, beautiful and concise;
2.Circuit breaker can defense all kinds of environmental impact because of its used vertical insulation sleeve,Therefore circuit breaker can be applied to all kinds of special environmental conditions;
3.Fixed and handcart types can satisfy different equipped requirements for cabinet and circuit breaker;
4.Few maintenance,Usually the operating mechanism only need doing a bit of cleaning or lubrication.
The normal conditions
- Ambient temperature: max +40°C min -15ºC(conveyance under -30ºC is allowed);
- Altitude: ≤1000m;
- Relative humidity: daily average relative humidity: ≤95%; monthly average relative humidity:≤90%; daily average saturated vapor pressure: ≤2.2*10-3 MPa; monthly average value :≤1.8*10-3 MPa;
- Earthquake intensity: ≤8 degree;
- The installation site should be no explosion,severe vibration,chemical corrosion and serious pollution. Main technical data
No. |
Items |
Unit |
Value |
1 |
Rated voltage |
KV |
12 |
2 |
Rated insulation level |
Rated lighting impulse withstand voltage (peak) |
KV |
Phase,over the ground 75,fracture80 |
Short-time power frequency withstand voltage(1min) |
KV |
Phase,over the ground 42,fracture48 |
3 |
Rated short circuit breaking current |
KA |
20 |
25 |
31.5 |
40 |
4 |
Rated current |
A |
630 1250 |
630 1250 1600 2000 2500 3150 |
1250 1600 2000 2500 3150 4000 |
5 |
Rated thermo stability current(valid) |
KA |
20 |
25 |
31.5 |
40 |
6 |
Rated dynamic stability current(peak) |
KA |
50 |
63 |
80 |
100 |
7 |
Rated short-circuit making current(peak) |
KA |
50 |
63 |
80 |
100 |
8 |
Rated operations of short-circuit breaking current interruption |
Times |
50(40KA as 30) |
9 |
Power frequency withstand voltage of secondary circuit(1 min) |
V |
2000 |
10 |
Rated operating sequence |
|
opening-0.3S-closing opening-180S- closing opening /opening-180S- closing opening -180S- closing opening (40KA) |
11 |
Rated thermo stability time |
S |
4 |
12 |
Rated breaking current(a capacitor/back to back capacitor) |
A |
630/400 800/400(40KA) |
13 |
Mechanical life |
Times |
30000 |
Note:When the rated current reached 4000A, You need enforce air cooling.