Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Still deciding? Get samples of US$ 910/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Main Technical Data | ||
Rated voltage | kv | 40.5 |
Rated current | A | 1600/2000/2500/3150 |
Rated frequency | Hz | 50 |
Rated short-circuit breaking current | kA | 31.5 |
Operations of short-circuit breaking current interruption | times | 30 |
Rated short-circuit making current | kA | 80 |
Rated short-time withstand and current(4s) | kA | 31.5 |
Rated single capacitor bank breaking current | A | 630 |
Rated back-to-back capacitor bank breaking current | A | 400 |
Short-time(1min) power-frequency withstand voltage | kv | 95 |
Rated lighting impulse withstand voltage(peak) | kv | 185 |
Machanical life | times | 30000 |
Contact closing force due to bellows and atmosphere | N | 250±50 |
Counterforce at rated contact force | N | 330±50 |
Circuit resistance at rated contact force | μΩ | ≤20 |
Shelf life | years | 20 |
Part discharge | pc | ≤5 |
Rated operating sequence | 0-0.3-CO-180s -CO | |
Mechanical Data of Circuit-Bearking Equipped with the Interrupters | ||
Contact erosion limit | mm | 3 |
Rated contact stroke | mm | 18±1 |
contac connection stroke | m/s | 4±1 |
Average opening speed | m/s | 1.6±0.2 |
Average closing speed | m/s | 0.8±0.2 |
Added contact force | N | 3150±200 |
Bounce duration of contact closing | ms | ≤2 |
Out of simultaneity of contact closing and opening | mm | ≤1 |
Max.overtravel | ms | ≤2 |
Note:Rated characteristics can be given on requirment |