Customization: | Available |
---|---|
Electricity Type: | Vacuum |
Number of Pole: | 3 |
Still deciding? Get samples of US$ 60/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Vacuum Interrupter for Contactor
Vacuum arc extinguishing chamber, also known as vacuum switch tube, is the core component of the high voltage power switch, its main role is to cut off the arc and inhibit the electric current by its high inside insulation performance to avoid accidents.
Wuhan Feite Electric brand vacuum arc extinguishing chamber adopts a corrugated ceramic insulation shell, copper tungsten tungsten carbide alloy materials contact, using advanced one exhuast technology process makes the vacuum interrupter has the advantages of small volume, high insulating level, low closure value, long service lifetime, easy-maintenance, explosion-free, low noise, low maintenance costs, reliable operation and non-pollution etc.. The vacuum arc extinguishing chamber mainly been used in power transmission and distribution control system. It is also can be used in metallurgy, mine, petroleum, chemical industry, railway, broadcasting, communications, industrial high frequency heating power distribution system.
Wuhan Feite Electric vacuum arc extinguishing chamber for vacuum contactor rated voltage is 1.14~40.5kV, rated current is 630A~1250A
Main Technical Date--ZKTJ2500/3.6-10
Parameter item | Unit | Data |
Rated Voltage | kV | 3.6 |
Rated Current | A | 2500 |
Rated Frequency | Hz | 50 |
Rated Short-time Power Frequency Withstand Voltage(1min) | KV | 21 |
Rated Lighting Impulse Withstand Voltage | kV | 40 |
Rated Making Current | kA | 10 |
Rated Breaking Current,Max | kA | 8.0 |
Rated Breaking Current,Min | kA | 250 |
Rated Making Current,Limit | kA | 10 |
Rated Short-time Withstand current | kA | 8.0 |
Rated Duration of Short-circuit | s | 4 |
Mechanical Life | times | 30000 |
Electricity Life AC-3 | times | 250000 |
Electricity Life AC-4 | times | 100000 |
Rated Contactl Stroke | mm | 3±0.5 |
Contact Closing Force Due to bellows and atmosphere | N | 150±30 |
Counterforce at rated contact stroke | N | 200±40 |
Circuit resistance at rated contact atmosphere force | µ | ≤50 |
Shelf life | year | 20 |
Contact erosion limit | mm | 3 |
Weight of moving parts | kg | ≤0.8 |
Parameter item | Unit | Data |
Added contact force | N | 2000±100N |
Average opening speed | m/s | 0.6±0.2 |
Average closing speed | m/s | 0.3±0.1 |
Contact Bouncing Duration at closing operation | m/s | ≤2 |
Contact Bouncing Bank Amplitude of Opeing Operation | mm | ≤2 |
Three-pole simultaneity | ms | ≤1 |
ABOUT OUR COMPANY
Wuhan Feite Electric Co.,Ltd is located at Wuhan city, Hubei Province which is the Eastcenter part of China. lt is specialized in producing vacuum interrupter and vacuumembedded poles.The company has developed 1.14KV-40.5KV vacuum switch tubes morethan 300 types,which can be widely used for various vacuum circuit breaker, vacuumcontactors, vacuum load breaker switches, auto re-closers,RMU etc.The company has full sets vacuum producing and testing equipment,with annualproduction of 600,000 vacuum tube production capacity, As an ISO09001:2008 certifiedcompany,our production process strictly conforms to quality management system.Wuhan Feite Electric Co.,Ltd is always supply you good quality products with reasonableand competitive prices.
1. Precheck before putting it into use.
Check id packing is in good condition. Check the appearance of vacuum interrupter and
Whether it corresponds to the test certificate after uppacking. When shaking the interrupter, the ceramic envelop should be integrated.Power frequency withstand voltage should be tested before operating vacuum interrupter. Clean the surface with a dry colth or alcohol damped cloth before testing. The normal way for testing is an follows: when in the clearance between open contacts applies with 70 percent of rated power frequency withstand voltage within 1 min. The vacuum interrupter will be qualified if there is no sudden change and trip phenomena in the pointer of the vacuum interrupter.
2. Mounting of vacuum interrupter
a.Clean the surface of vacuum interrupter with cotton or alcohol dipped silk cloth before mounting. Meanwhile clean the conducting pole and surface of electric connection in order that the vacuum interrupter can have good electric contact with the equipment.b.The interrupter should be adjusted in the line with the equipment after mounting. The mechanical date related to the interrupter must meet the given specification.
3.In mounting, attention should be paid to the following:
a.When operating, guide unite unit must be provided for the interrupter. The coaxality of moving conducting pole and axial line of interrupter must meet the requirement. There should not be torque force applied on the bellow.
b. When mounting, it is forbidden to beat or strike the interrupter envelop with hard things in case crack may occur to cause air leakage.
c.Take care to assure that the conducting pole must be coaxial with interrupter, and that the conducting pole must be vertical on the face of fixed end
d.Take care not to disassemble the interrupter repeatedly to prevent screw from slipping. There should not be twisting on the moving conducting pole and over press on bellow to avoid that any torque force and scratch may occur to bellow to reduce its service life.
e.During mounting, the force applied on the face of both ends should not go beyond the static relief pressure stipulated in the specification.
4. Application.
a. Check the vacuum interrupter periodically by the way power frequency withstand voltage. For this, please see subclause
b. Periodically check how burnout is going on for contacts. When it comes to the burnout mark of moving conducting pole, it shows that the vacuum interrupter has finished its electrical endurance, and it should be replaced.